beautypg.com

11) ventilation, 12) lighting and shutdown instructions – Space Ray DK Series User Manual

Page 14

background image

Form #43219010

Sept 2012

11) VENTILATION

Where unvented infrared heaters are used, natural or mechanical means shall be provided to supply and exhaust
at least 4 cfm per 1000 Btu per hr input of installed heaters.

Exhaust openings for removing flue products shall be above the level of the heaters.

This heater requires ventilation in the building to dilute the products of combustion and provide fresh air for
efficient combustion. Power ventilation is recommended and the minimum vent flow required is as follows:


DK30, DK33, DK35


140 cfm


DK100


400 cfm

DK40

160 cfm

DK120

480 cfm

DK60, DK66, DK70

280 cfm

DK132, DK140

560 cfm

DK80

320 cfm

DK160

640 cfm

If gravity ventilation is used, the required square feet of inlet and outlet vent area (depending on height and
temperature difference) is as follows:


DK30, DK33, DK35


0.49 s/f


DK100


1.48 s/f

DK40

0.57 s/f

DK120

1.72 s/f

DK60, DK66, DK70

0.98 s/f

DK132, DK140

1.97 s/f

DK80

0.98 s/f

DK160

2.30 s/f

The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating
vents. Exhaust vents must be located at the highest point above and in the vicinity of the heaters and the inlet
vents must be located below the level of the heaters. Inlet openings in the building should be well distributed high
in the sidewalls and should direct incoming air upward to dilute products of combustion while preventing drafts at
lower levels. Inlets are typically 1 to 3 sq. ft. Local codes may require that mechanical exhaust systems be
interlocked with the function simultaneously or allow control of exhausters to humidistat.

12) LIGHTING AND SHUTDOWN INSTRUCTIONS







13