Seaward PV System User Manual
Page 4
![background image](https://www.manualsdir.com/files/804207/content/doc004.png)
Page 4 of 4
Seaward Solar, 6304 Benjamin Road, Suit 506, Tampa, Florida 33634, USA.
Tel: (813) 886 2775 Email: [email protected] Web: www.seawardsolar.com
© 2012 Seaward Electronic Ltd.
All rights reserved
Rev 2: 15.02.2012
The methods for performing these tests are generally familiar to all electricians. However,
difficulties may arise if the technician is unaware of the extent to which PV circuits need to be
segmented and isolated for these tests to be performed properly. Therefore, it is important that
anyone performing these tests be specifically qualified with regard to PV systems.
Combinations of standard electrical test equipment can be used to complete the required tests, such
as a megohm meter paired with either a digital multimeter or a clamp meter. Increasingly,
specialized test equipment is available for PV applications. For example, the PV100 solar installation
test kit from Seaward Solar includes everything needed to test to IEC 62446: a continuity and
insulation resistance tester, a digital multimeter and a dc current clamp.
While IEC 62446 does not specify the order of the tests, there is logic behind the order that it
recommends. For example, if equipment is properly bonded to earth, then it is inherently safer to
work around in the event of a fault; and if polarity tests are not completed before functional tests
are performed, then equipment may be damaged at start-up due to reverse polarity or overvoltage.
Note that in the event that a test indicates a fault, the standard requires that all previous tests be
repeated after the fault is rectified. This is because the fault may have influenced earlier test
results.
The subsections related to the
specific dc circuit tests provide
instructions on how to perform the
verification tests, as well as how to
interpret the results. For example,
IEC 62446 describes two short-
circuit test procedures, the results
of which can be measured using
either an in-line or a clamp-on
ammeter. Similarly, two test
methods are provided for the PV
array insulation test, as well as a
recommended procedure and a
table for interpreting the results
(see Table 1).
Test Method
System Voltage (Voc
stc x 1.25)
Test Voltage
Minimum Insulation
Resistance
<120v
250v
0.5MΩ
120 – 500v
500v
1MΩ
Test Method 1
Separate tests to
Array positive and
Array negative
<500v
1000v
1MΩ
<120v
250v
0.5MΩ
120 – 500v
500v
1MΩ
Test Method 2
Array positive and
negative shorted
together
>1000v
1000v
1MΩ
Table 1: Insulation resistance test results are satisfactory, according to the test methods
and procedure outlined in IEC 62446, if they are not less than the values shown here.