Sccg50 & sccp50 service manual – Scotsman SCCG50 User Manual
Page 27

Service Diagnosis
No Ice
Problem
Likely Cause
Probable Solution
No power to unit
Power disconnected
Check breaker or fuse. Reset or
replace, restart and check
No power to controller
Transformer open
Replace transformer
Control panel open
Switch failure
Test ribbon cable, see page 32
Shut down on maximum
water fill time - water light
flashing
Water shut off
Restore water supply
Very long freeze cycle
Water leak
Check curtain, sump
Dirty condenser
Clean condenser
Restricted location, intake air too
hot or blocked
Eliminate restriction, have machine
moved
Evaporator thermistor not sensing
properly
Check thermistor
Spray jets dirty
Remove spray platform and clean
spray jets
Inlet water valve leaks through
during freeze
Check inlet water valve
Low on refrigerant
Check cube formation,
Connected to hot water
Check for bleed thru from missing /
broken check valve in building
water supply
Cannot make ice
Spray pump not pumping
Check pump motor
Fan motor not turning
Check fan motor, check fan blade,
check controller for voltage output
Pump hose disconnected
Check hose
Very low on refrigerant
Add access valve, add refrigerant
as a test. If unit makes ice, find and
correct leak.
Compressor not operating
Check compressor start
components, check PTCR
resistance and temperature
Check compressor voltage
Check compressor windings
Hot gas valve leaks through during
freeze
Check hot gas valve for hot outlet
during freeze
Compressor inefficient
Check compressor amp draw, if low
and all else is correct, change
compressor
January 2012
Page 26
SCCG50 & SCCP50
Service Manual