SERVICE DIAGNOSIS: Refrigeration and/or Mechanical

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

Poor harvest

Hot gas valve does not open

Check for power to the coil, check for
not opening, replace

Head pressure control valve does not
maintain enough head pressure.

Replace head pressure control valve.

Unit cycles off during freeze or
harvest

Hi temperature switch opens and
closes

Hot gas valve leaks thru, replace it

Low capacity

High head pressure, from dirty
condenser, faulty fan motor

Clean condenser, repair fan motor

Non condensable gas in the system

Purge system, evacuate and weigh in
nameplate charge

Extreme hot location

Relocate the cabinet

Overcharge of refrigerant

Evacuate and weigh in nameplate
charge

Hot gas valve leaks thru

At the end of the freeze cycle there
should be frost on the evaporator end
of the hot gas tubes, if not replace the
hot gas valve

Liquid and discharge lines are in
contact with each other

Separate and insulate them

Unit shuts off before bin is full

Bin Ice level control is set to “Partial”

Move bin Ice level rocker switch to
“Full”.

Compressor cycles on and off

Low pressure control opening and
closing

Check low side pressure, liquid line
valve must open and low side
pressure raise over 35 PSIG before
pump down control will close to run
compressor

Compressor overheats

TXV not letting enough refrigerant
into evaporators, adjust or replace
TXV

Mechanical fault with compressor,
replace compressor

Frost on compressor

Some frost will not hurt

Do nothing

TXV meters too much refrigerant

Adjust or replace TXV

MCM1462R