Class 1, Fig. 9, Fig. 10 – Royal Cozyfires Slimline Standard MK2 - LPG User Manual

Page 9: Class 2, Fig. 11, Pre-cast

background image

MM79 010710

2.4.1

INSTALLING

THE

APPLIANCE

(Flue)


Any permanent flue restriction must be removed and any variable dampers locked fully open or removed. If the flue has been used
previously for solid fuel, it must be swept PRIOR to installation. This appliance is suitable for installation into CLASS 1, Class 2 and
PRE-CAST flues.







































Page 8

505mm

410/460mm

555/590mm

Hatched area must be non-combustible and

flat to ensure a seal around the appliance.

Class 1


A conventional brick or stone chimney with a minimum effective cross
sectional dimension of 225mm x 225mm.

A lined flue with a minimum diameter of 175mm having a chair brick and
throat lintel conforming to the current issue of BS 1251 (Fig. 9).

If a chair brick is fitted, the minimum distance from the knee to the front face
of the surround is 150mm.

If no chair brick is fitted, the minimum distance required between the rear of
the opening and the front face of the surround is 210mm

NOTE: A restrictor plate is supplied with the IFU kit. This restrictor plate
MUST ONLY BE USED ON THIS FLUE TYPE!

Fig. 9

600mm

600mm

500mm

410mm

555mm

Hatched area must be non-

combustible and flat to ensure a

seal around the appliance.

Fig. 10

The area beneath the metal flue box

must be a non-combustible material

25mm thick.

Class 2

A twin walled metal flue box manufactured to the current
issue of BS 715 with a twin walled 125mm diameter flue
and a minimum effective height of 3 metres (Fig 10).

NOTE: The restrictor plate supplied in the IFU kit MUST
NOT BE USED ON THIS FLUE TYPE!

500mm

410mm

555/590

mm

Hatched area must be non-combustible

and flat to ensure a seal around the

appliance.

Fig. 11

600mm

Pre-Cast

A pre-cast flue conforming to the current issue of BS
1289 and BS 1289 Part 1 including properly constructed
pre-cast flues with a cross sectional area of 13000mm

2

(Fig. 11).

NOTE: The restrictor plate supplied in the IFU kit MUST
NOT BE USED ON THIS FLUE TYPE!

Surround thickness
when flue outlet
depth is maintained

Care must be taken to

ensure that the flue

spigot from the

appliance does not

impede the flue outlet

from the metal box

Care must be

taken to ensure

that the flue

spigot from the

appliance does

not impede the
flue outlet from

the metal box