Wiring – Remotec ZTS-110 V3.12 User Manual
Page 8

7
Wiring
- Be sure the operation mode is OFF 
 and Fan selection is Fan Auto
- Wire the proper cables at the terminal 
 block according to the circuit diagram
- Afterward, push all cables back into 
 the wall
- Do not use metal conduit or of cable 
 provided with a metal sheath
- Recommends adding fuse or 
 protective device in the line circuit 
Important!
If you will be powering the ZTS-110 with 24Vac:
Connect the "24Vac Common" (typically the black wire/terminal) and "24Vac 
Power" (typically the Red wire/terminal) from the HVAC system to the ZTS-110 
HVAC System terminal block "C" and "RH" or "RC" terminals (see the following 
explanation, these may be jumpered together).
Common or Split Transformer Systems:
Most HVAC systems have a common heating and cooling transformer. You must 
insert a jumper wire to tie the RH and RC inputs together for this configuration. If 
you have a system with separate heating and cooling transformers, do not insert a 
jumper wire between RC and RH.
When wiring split systems, wire the heating systems "24Vac Power" (red wire) to 
the ZTS-110 "RH" terminal, and wire the cooling systems "24Vac Power" to the 
ZTS-110 "RC" terminal. Also wire the cooling systems "24Vac Common" to the 
ZTS-110 "C" terminals.
Note: Do not split RC/RH for Heat Pump systems!
Figure 4. Non-heat pump (Standard Gas or Electric) HVAC system wiring
Terminals
Cool changeover (heat pump)
Heat changeover (heat pump)
2nd Stage heater
1st Stage heater
Fan
Compressor
24Vac Common
24Vac Power for Cooling
24Vac Power for Heating
Symbol
O
B
W2
W1
G
Y
RC
RH
C
Standard HVAC System
nd
W2 - 2 stage heater
st
W1 - 1 stage heater
G - Fan
Y - Compressor
R - 24Vac Power
C - 24Vac Common
O
B
W2
W1
G
Y
RC
RH
C
Brown
White
Green
Yellow
Red
Black
ELECTH
HPUMP
J2