Remko – REMKO Elektric Booster Heater User Manual

Page 6

background image

6

REMKO

ELECTRIC BOOSTER HEATER FOR

HEAT PUMP STORAGE TANK

Installation may only be performed

by authorised specialists.

NOTE

1. Empty the storage tank on the

water side.

2. Remove the corresponding

blanking plug on the tank.

For possible positions, see page 8.

3. Use hemp to seal the electric

heating coil.

4. Screw the heating coil into the

selected screw-in fitting.

5. Fill up the water side and bleed the

storage tank and, if necessary the
whole system.

6. Perform leak testing on the system.

7. Insert the cables into the

electrical switch cabinet.

1. Open the electrical switch

cabinet in the indoor unit.

2. Place the contactor provided

on site on the top-hat rail in

the switch cabinet.

3. Connect the following wires:

- Phase L from terminal X1.1 to

terminal X2.4

- Wire from terminal X2.5 to

contactor A1

- Wire from contactor A2 to

terminal X1.2


Mains supply from sub-distribution:

- Connect to following contactor

contacts

L1 to 1

L2 to 3

L3 to 5

Connect booster heater supply

to contactor contacts

L1 to 2

L2 to 4

L3 to 6

4. Close cable ducts and the

electrical switch cabinet.

5. Set the system temperature on the

thermostat on the heating element
and the bivalence point in the heat
pump manager, while noting the
required supply temperature of your
heating system.

6. Reattach the housing panels

and put back into service.

Installing the electric

booster heater in the

storage tank

Electrical connection