Troubleshooting – REMKO CMF-80 v.1 User Manual

Page 11

background image

Troubleshooting

The unit has been manufactured using state-of-the-art production
methods and tested several times to ensure its correct function. However,
in the event that malfunctions should occur, the device should be checked
against the following list. Please inform your dealer if the unit is still not
working correctly after all of the functional checks have been performed.

Control lamp

Meaning

Remedy

red

Heat pump fault

briefly switch the plant off and wait for restart /

inform your specialist dealer or engineer

yellow

Flow monitor fault

Check the function of the condenser pump or

flow monitor / check system pressure and flow

white

Energy supply company off-period

The heat pump can be configured to switch

on automatically as required according to

a contractually regulated power off period.

Fault

Possible causes

Remedy

The heat pump does

not start or switches

itself off

Power outage, undervoltage

Check the voltage and, if necessary, wait for it

to come back on

Defective mains fuse

Master switch off

Exchange mains fuse, switch master switch on

Power cable damaged

Repair by specialist firm

Energy supply company off-period

Wait until the off-period is over and the heat

pump starts up as required

Operational temperature range too

low or exceeded

Observe temperature ranges

Setpoint temperature exceeded

Incorrect mode

The setpoint temperature has to be higher than

the heating appliance temperature, check mode

Heat circuit pump

fails to switch off

Incorrect pump switching

Arrange to have pump switching checked in

"heating circuit" expert level

Heat circuit pumps fail

to switch on

Incorrect mode set

Check mode

Fuse on control PCB in indoor

module switching cabinet faulty

Exchange the fuse on the left side of the

control PCB

Incorrect heating program set

Check heating program

Temperature overlapping, e.g.

external temperature greater than

room temperature

Observe temperature ranges

NOTE

During the power plant

operator off period, "Info 55"

is displayed (heat pump off

period).