beautypg.com

Technical data vrs b – REMKO VRS 20 User Manual

Page 15

background image

15

Technical Data VRS B

R E M K O V R S

4 0

6 0

8 0

1 2 0

1 5 0

2 1 0

2 5 0

3 1 0

3 8 0

4 5 0

Rated heat power

kW

44

60

88

132

165

222

276

330

413

495

Rated heat output

kW

40

55

80

120

150

200

250

300

375

450

Rated air output

1)

m³/h

3.400 4.650 6.800 9.750 11.700 15.700 19.300 23.600 29.500 35.200

Rated pressure, external

2)

Pa

50

80

70

120

60

80

80

90

120

110

Fuel

Oil throughput (heating oil EL)

kg/h

3,7

5,1

7,4

11,1

13,9

18,7

23,3

27,8

34,8

41,6

Gas throughput (natural gas H) m³/h

4,2

5,8

8,5

12,7

15,9

21,4

26,6

31,8

39,8

47,7

Gas throughput (natural gas L) m³/h

5,0

6,8

9,9

14,9

18,7

25,1

31,2

37,4

46,8

56,0

Gas throughput (liquid gas)

m³/h

1,7

2,3

3,4

5,1

6,4

8,6

10,6

12,7

Exhaust mass current V

Af

3)

kg/h

68

93

134

200

250

332

415

500

622

748

Exhaust temperature approx.

4)

°C

195

200

195

195

200

205

205

200

200

200

Required chimney draught

Pa

0

0

0

0

0

0

0

0

0

0

Exhaust loss VA max

%

9

9

9

9

9

9

9

9

9

9

Furnace resistance

Pa

18

18

32

29

54

66

55

60

60

65

Electrical connection

2)

V

230/1~ 230/1~ 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N 400/3N

Frequency

Hz

50

50

50

50

50

50

50

50

50

50

Rated current

2) 5)

A

4,5

5,5

2,65

3,6

5,1

6,8

8,8

11,4

8,8/8,8 8,8/8,8

Power consumption

2) 5)

kW

0,51

0,75

1,1

1,5

2,2

3,0

4,0

5,5

4,0/4,0 4,0/4,0

Power consumption

6)

W

210

210

210

450

450

350

350

350

1900

1900

Exhaust gas connection Ø

mm

150

150

180

180

180

200

250

250

300

300

Weight

7)

kg

190

260

305

365

450

680

735

930

1055

1240

H e a t i n g o i l E L o r n a t u r a l / l i q u i d g a s

Heating value H

i

in its normal state

heating oil EL 11,86 kWh/kg
natural gas H 10,38 kWh/m³
natural gas L 8,83 kWh/m³
liquid gas 25,89 kWh/m³
liquid gas 12,87 kWh/kg

Max. suction temperature 40 °C / max. outgoing temperature 100 °C

1) air current at

t

40 K / 1,2 kg/m³

2) for standard compression
3) approx. quantity for oil operation
4) measured temperature minus room temperature
5) unit without burner
6) for factory-installed burner
7) for standard model, without burner and other accessories

We reserve the right to make modifications in dimensions and construction in the interests of technical progress.