Technical Data VRS INOX

2 5

5 0

7 5

1 0 0

1 3 0

1 7 0

2 0 0

Rated heat power

kW

33

62

89

125

160

208

249

Rated heat output

kW

29

57

83

116

149

193

232

Rated air output

1)

m³/h

1.760

3.950

5.270

7.950

9.800

12.000

13.900

Rated pressure, external

Pa

110

60

100

80

100

50

70

Fuel

Heating oil EL or natural/liquid gas

Oil throughput (heating oil EL)

kg/h

2,8

5,2

7,5

10,6

13,5

17,5

21,0

Gas throughput (natural gas H) m³/h

3,2

6,0

8,6

12,1

15,4

20,0

24,0

Gas throughput (natural gas L)

m³/h

3,8

7,0

10,1

14,2

18,1

23,5

28,2

Gas throughput (liquid gas)

m³/h

1,3

2,4

3,4

4,9

6,2

8,0

9,6

Exhaust mass current V

Af

2)

kg/h

50

95

138

190

245

320

385

Exhaust temperature approx.

3)

°C

160–190 160–190 160–190 160–190 160–190 160–190 160–190

Required chimney draught

Pa

0

0

0

0

0

0

0

Exhaust loss VA min./max.

%

7 / 9

7 / 9

7 / 9

7 / 9

7 / 9

7 / 9

7 / 9

Furnace resistance

Pa

6

8

18

20

25

31

38

Sound pressure level L

pA 1m

4)

dB(A)

57

58

63

60

65

65

65

Electrical connection

V

230/1~

230/1~ 400/3N~ 400/3N~ 400/3N~ 400/3N~ 400/3N~

Frequency

Hz

50

50

50

50

50

50

50

Rated current

5)

A

2,2

2,6

2,8

3,7

3,7

3,7

5,2

Power consumption

5)

kW

0,25

0,25

1,1

1,5

1,5

1,5

2,2

Power consumption

6)

kW

0,46

0,46

1,55

1,95

1,95

1,84

2,54

Exhaust gas connection Ø

mm

150

150

180

180

200

200

200

Weight

7)

kg

150

240

310

360

550

730

820

R E M K O V R S

18

16,7

1.050

62

Heating oil EL

1,52

n/a

n/a

n/a

28,5

170–180

0

7 / 10

8

58

230/1~

50

1,1

0,17

0,28

150

90

2 0

1) air current at

t

40K / 1.2 kg/m³

2) approx. quantity for oil operation
3) measured temperature minus room temperature
4) noise measuring (without burner) DIN 45635-01-KL3
5) unit without burner
6) with manufacturer-supplied burner
7) for standard model, without burner and other accessories

Heating value H

i

in its normal state

heating oil EL 11,86 kWh/kg
natural gas H 10,38 kWh/m³
natural gas L 8,83 kWh/m³
liquid gas 25,89 kWh/m³
liquid gas 12,87 kWh/kg

Max. suction temperature 40 °C / max. outgoing temperature 100 °C

We reserve the right to make modifications in dimensions and construction in the interests of technical progress.