Technical Data
REMKO VRS I
Standard compression
Typ
25
Typ
50
Typ
75
Typ
100
Typ
130
Typ
170
Typ
200
Rated heat power
kW
33
62
89
125
160
208
249
Rated heat output
kW
29
57
83
116
149
193
232
Rated air output
1)
m³/h
1.760
3.950
5.270
7.950
9.800
12.000
13.900
Fuel
Heating oil EL or natural/liquid gas
Oil throughput (heating oil EL)
kg/h
2,8
5,2
7,5
10,6
13,5
17,5
21,0
Gas throughput (natural gas H) m³/h
3,2
6,0
8,6
12,1
15,4
20,0
24,0
Gas throughput (natural gas L)
m³/h
3,8
7,0
10,1
14,2
18,1
23,5
28,2
Gas throughput (liquid gas)
m³/h
1,3
2,4
3,4
4,9
6,2
8,0
9,6
Exhaust mass current V
Af
2)
kg/h
60
115
170
220
290
380
440
Exhaust temperature approx.
3)
°C
160–190
Required chimney draught
Pa
0
Exhaust loss VA min. / max.
%
7 / 9
Furnace resistance
Pa
6
8
18
20
25
31
38
Sound pressure level L
pA 1m
4)
dB(A)
57
58
63
60
65
65
65
Electrical connection
V
230 / 1~
400 / 3~ N
Frequency
Hz
Rated current
5)
A
2,2
4,5
2,8
3,7
3,7
3,7
5,2
Power consumption
5)
kW
0,20
0,515
1,1
1,5
1,5
1,5
2,2
Power consumption
6)
kW
0,21
0,21
0,45
0,45
0,45
0,34
0,34
Exhaust gas connection Ø
mm
150
150
180
180
200
200
200
Weight
7)
kg
150
240
310
360
550
730
820
50
1) Air current at
∆
t
40K / 1,2 kg/m³
2) Approx. quantity for oil operation
3) Measured temperature minus room temperature
4) Noise measuring (without burner) DIN 45635-01-KL3
5) Unit without burner
6) For manufacturer-supplied burner
7) For standard model, without burner and other accessories
Max. suction temperature 40 °C / max. outgoing temperature 100 °C
We reserve the right to make modifications in dimensions and construction in the interests of technical progress.