Technical data – REMKO ATR-3 User Manual
Page 15

15
Technical Data
Temperature range
(Day and night temperature)
0 to 30°C, adjustable; to 5 to 30°C
can be limited by an internal setting
Temperature difference dT
1 to 10K, adjustable
Proportional control Xp
1 to 5K, adjustable
Heating
-1 to -10K, distance from target value
adjustable
Clock timer
Electronic weekly clock timer,
power reserve clock approx. 10 minutes,
program is permanently saved
Sensor
KTY semi-conductor sensors (polarised)
Operating current
230V AC, +10%, -15%
Internal consumption
approx. 5 VA
Outputs: Fan output
approx. 80 to 230 V gradually increasing
current (phase control) for the fan
Heating relay
isolated contact (shutter)
Additional relay
isolated contact (two-way contact)
(switches on/off with phase control)
Analog output
0-10V, parallel to the phase control (Xp)
Max. line load currents
6,3A, 230V AC fan on the phase control
10 (4)A, 250V AC heating relay
2 (2)A, 250V AC additional relay
1 mA max. on the analog output (0...10 V)
Housing Dimensions
242 x 185 x 115 mm (W x H x D)
Attachment
wall-mounted
Protection type
IP 54 (protected from spraying water)
Protection class Il in accordance with DIN EN 60335-1
Weight
approx. 1500 g