Troubleshooting

– unit doesn’t start

– unit stops during operation

– fan blows but gas supply is blocked
or the flame does not ignite

– flame goes out after the pin of
thermoelectric gas valve is released

– gas supply is blocked or the flame goes out

– fuel consumption is too high

– unit can’t be shut down

– heating capacity diminishes during continuous operation

1 – 2 – 3 – 4 – 7

2 – 4 – 7 – 12 – 13

4 – 5 – 8 – 9 – 12


8 – 10 – 11


4 – 6 – 7 –10 – 11 – 12 – 13

12 – 15

3 – 14

13

Cause:

Problem:

Cause:

Remedy:

1. no electrical connection

-

plug the unit into an appropriate mains socket (230V/1~ 50Hz)

2. fan motor is overloaded

(fan blows irregularly or is blocked)

-

check fan motor, fan blade and clutch plate and replace if necessary.

3. operating switch is defective

-

shut off gas supply, unplug the unit and replace defective operating
switch

4. no gas pressure on solenoid valve

-

check gas supply

-

check contents of gas cylinders

-

check gas hose(s) for damage

-

release hose break protection resp. replace it

5. no ignition spark

-

set ignition electrode

-

check ignition cable

-

check porcelain insulation of ignition electrode

6. Air suction grille is dirty

-

clean air suction grille

7. unit is shut down by safety temperature limiter (STB)

-

check air suction and blow-out grille and clean if necessary

-

check fresh air supply

-

release safety thermostat (STB - Reset)

8. safety pilot does not open or does not lock

-

replace safety pilot

9. piezo igniter is defective

-

replace piezo igniter

10. thermocouple is not getting warm enough

-

check position of thermocouple and adjust according to setting in-
structions

11. loose or dirty connection between safety pilot and thermocouple

-

check connection and clean if necessary

12. pressure controller defective or improper pressure controller at-

tached or hose breakage protection is blocked

-

attach original pressure controller

-

release hose breakage protection or replace it

13 ice has formed on the gas cylinder(s) due to low temperatures

and too much gas output

-

replace empty gas cylinder(s) and connect 2-3 cylinders using multi
cylinder set (Ref-No. 1014050)

14. solenoid valve does not open

-

shut off gas supply

-

let flame burn out

-

set operating switch to “0” and unplug the unit

-

replace solenoid valve

15. gas hose(s) are leaking

-

find leakage using foam substance to eliminate leaks

Shut off the gas supply and unplug the unit from the power supply before performing any work on the unit!

Adjustments or maintenance work may only be performed by authorised personnel!

*

*