Remko md – REMKO MD 261 User Manual

Page 20

background image

The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when loosening the
union nuts.

CAUTION

Connection of refrigerant
pipes

The on site connection of the
refrigerant pipes is made inside the
unit.

It may be necessary to fit a reducer
or flared adapter to the indoor
unit. These fittings are included
as standard. Once installed, the
connections should be made tight
against vapour diffusion.

The following instructions describe
the installation of the refrigerant
circuit and the assembly of the
indoor unit and the outdoor
component.

1. The required pipe diameters are

given in the table "Technical
data".

2. Remove the factory-fitted

protective caps and union
nuts on the connections.
These should be used during
installation.

3. Before flanging the refrigerant

pipes, ensure that the union nut
is fitted on the pipe.

4. Prepare the laid refrigerant

pipes as shown below
(Figure 6+7).

Only employ tools and
components suitable for
refrigeration applications.

NOTE

Flanging tool

7 Flanging the refrigerant pipe

Refrigerant pipe

Deburrer

6 Deburring the refrigerant pipe

8 Correct flange shape

Tighten 1. spanner

Counter

2. spanner

9 Tighten the fitting

Tightening

torque:

1 4

“ 15-20 Nm

3 8

“ 33-40 Nm

1 2

“ 50-60 Nm

5 8

“ 65-75 Nm

3 4

“ 95-105 Nm

5. Verify that the shape of the

flange is correct(Figure 8).

6. First connect and hand-tighten

the refrigerant connections
to ensure they are correctly
seated.

7. Now fully tighten the fittings

using 2 suitably sized open-
ended spanners. Use one
spanner to counter the force
when tightening the fitting
(Figure 9)

.

8. Use insulation hoses which are

designed for this temperature
range and diffusion tight.

9. Lay the refrigerant pipes from

the indoor unit to the outdoor
component. In doing so, ensure

that they are sufficiently

attached and take measures for
the oil return, if necessary!

10. Observe the permitted bending

radius for the refrigerant pipes
during installation. Never bend
a pipe twice in the same place.
Brittle pipes and potential
cracking are the consequences.

11. Use the wall or floor brackets

to fit the outdoor component
against structural parts
approved to support the static
load (refer to the installation
instructions for the brackets).

REMKO MD

20