Remko md, Installation instructions for qualified personnel – REMKO MD 261 User Manual

Page 16

background image

Problem display by blinker code

Display

Cause

Required action

E1

Communication error between outdoor component and indoor unit Contact specialist firm

E3

Liquefier fan controller faulty

Contact specialist firm

E5

Sensor evaporator temperature faulty / short-circuited

Contact specialist firm

E6

Sensor air circulation faulty / short-circuited or

sensor evaporator faulty / short-circuited

Contact specialist firm

H4

Operating limits of outdoor component or indoor unit

exceeded

Switch system off

P0

IGBT overvoltage protection

Contact specialist firm

P1

Undervoltage protection

Switch system voltage-free and switch on again

P2

Compressor overload protection

Contact specialist firm

P4

Power board IPM shutdown system

Contact specialist firm

Installation instructions for qualified personnel

Important points prior to
installation

Locate the unit in original
packaging as close as possible
to the installation point to avoid
transport damage.

Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report
any damage immediately to
your contracting party and the
shipping company.

Lift the unit at the corners
and not on the refrigerant or
condensation connections

The refrigerant pipes
(injection and suction pipe),
valves and connections must be
insulated impervious to vapour
diffusion. If necessary, insulate
the condensation pipe also

Select an installation location
which allows air to freely
flow through the inlet and
outlet. (See section "Minimum
clearances").

Do not install the unit in
the immediate vicinity of
devices with intensive thermal
radiation. Installation near
sources of thermal radiation
reduces the unit output.

Open the blocking valves of the
refrigerant pipes only after the
installation is complete.

Seal off open refrigerant pipes
with suitable caps or adhesive
strips to avoid infiltration of
moisture and never kink or
compress the refrigerant pipes.

Avoid unnecessary bends
. This minimises the pressure
loss in the refrigerant pipes and
ensures that the compressor
oil can flow back without
obstruction.

Make special preparations
regarding the oil return if the
outdoor unit is located above
the indoor unit. (See section
"Oil return flow measures").

Add refrigerant if the basic
length of the refrigerant pipe
exceeds 5 metres.

For the quantity of additional
refrigerant, refer to chapter
"Add refrigerant".

Only use the union nuts for
the refrigerant pipes provided
in the delivery scope, and
remove them just shortly before
connecting them with the
refrigerant pipes.

Make all electrical connections
according to valid DIN and DE
regulations.

See electrical connection
diagram. Always attach
electrical cables properly in
electrical clamps. Otherwise a
fire could result.

REMKO MD

16