beautypg.com

Remko mkt – REMKO MKT 250 User Manual

Page 6

background image

REMKO MKT

7

With low cleaning effort, you
can guarantee malfunction-free
operation and a long service
life.

Use only mild, environment-
friendly cleaning agents.

Regularly clean the
ventilation slots.

Clean the device as required,
but at least once a year, with
a moist cloth and lukewarm
water.

Do not expose the device to
direct water spray.

Maintenance and Care

Cleaning the air filter

Clean the air filter regularly,
but at least every 100 operat-
ing hours. In case of strongly
contaminated air, the period is
reduced accordingly.

1.

Switch off the device and
pull the mains plug.

2.

Remove the filter from the
device (Fig. 14).

3.

Clean the filter using a
vacuum cleaner or, in case
of heavy soiling, carefully
using lukewarm water (Fig.
15/16).

4.

Let the filter air-dry and then
reinsert it.

Fig. 14 Removing the air filter
upwards from the machine

CAUTION

Always turn off the device
and pull the mains plug before
cleaning!

Never operate the device
without the air filter.

Fig. 15 /16

Cleaning the air filter

Fig. 17 Draining the condensate

Draining the condensate

The condensate evaporates
during operation and is then
conducted outside with the
exhaust air via the air outlet
hose.

In case of extreme humidity,
the device collects conden-
sate in a reservoir. If the
permissible level is exceeded,
the red fault LED lights up
and the device shuts down.

The reservoir must be
emptied via the condensate
drain spout (Fig. 17).

Fig. 13 Functional principle of the cooling process

Functional principle of
the cooling process

The air conditioner
cools the air by re-
moving heat from it.
The fan (circulation
air) conducts cooled
air into the room. The
heat that the device
has removed from the
air is conducted out-
side via the air outlet
hose.

Ventilator

(exhaust air)

Evaporator

Condenser

Cooling circuit

Air inlet (exhaust air)

Air inlet (circulation air)

with air filter

Humidity is removed
from the air and drips
as condensate from the
evaporator onto the hot
condenser and evapora-
tes. Excess condensate
drips from the condenser
into a collection tray
and conducted from
there to the condenser
again using a rotor,
evaporated, and then
conducted away with
the exhaust air flow.

Cooled circulation

air in the room

Fan (circulation air)

Warm exhaust air

outside