2.8 Connector installation
 
A masonry flue connector may provide acceptable performance (Figure 2.8a); however, we recommend 
the use of a chimney liner (rigid or flexible) to ensure satisfactory performance (Figure 2.8b). To ensure 
an optimal draft, we also strongly recommend adding a minimum of 18” rigid liner between the roof 
flashing and the rain cap. Slip connectors for continuous liners should also be installed. Use Listed 
Chimney Liners – UL1777, CAN/ULC-S635. 
Figure 2.8a*
Figure 2.8b*
*
Generic illustrations. The model of your insert can differ from the one shown above.
ATTENTION INSTALLER: When positioning the unit in a fireplace opening prior to the flue 
installation, install the insert into the opening until the top lip of air jacket is flush with fireplace 
facing. 
 
If lag-bolts and anchors are to be used to secure the insert, the whole locations should be marked 
with the unit in place. Remove the insert and locate the anchors. 