If a non-combustible material floor protection needs to be added in front and level with the hearth
extension masonry fireplace (see Figure 2.6a), an R factor equal to or greater than 1.00 is required. If the
extension of the masonry hearth is raised at least 4" from the floor protection (see Figure 2.6b), a non-
combustible material without an R factor is sufficient.

Figure 2.6a

Figure 2.6b