beautypg.com

Osburn OB01801 User Manual

Page 12

background image

/12

The use of an R value is convenient when more than one material is going to be used in the hearth
extension to cover the combustible surface. This is because R values are additive, whereas K values are
not. To find the corresponding R factor to use for some selected materials, please see Table Thermal
characteristics of common floor protection materials
in this section.

There are two ways to calculate the R factor of the floor protection. First, by adding the R-values of
materials used, or by the conversion if the K factor and thickness of the floor protection are given.

To calculate the total R factor from R factors of the materials used, simply add the R-values of materials.
If the result is equal to or greater than the R-value requirements, the combination is acceptable. To know
the R-values of some selected materials, see table Thermal characteristics of common floor protection
materials
.

Example:

Required floor protection R of 1.00. Proposed materials: four inches of brick and one inch of
Durock

®

board

Four inches of brick (R = 4 x 0,2 = 0,8) plus 1 inch of Durock

®

(R = 1 x 0.52 = 0.52).

0.8 + 0.52 = 1.32.

This R value is larger than the required 1.00 and is therefore acceptable


In the case of a known K and thickness of alternative materials to be used in combination, convert all K
values to R by dividing the thickness of each material by its K value. Add the R values of your proposed
materials as shown in the previous example.

Example:

K value = 0.75

Thickness = 1

R value = Thickness/K = 1/0.75 = 1.33


Data for floor protection calculation

A

B

(Note 1)

C

E

Smaller

than 6 ft

2

*

Bigger or

= to 6 ft

2

*

INCHES

16"

20"

CAN: 18"

USA: 16"

5 3/8"

9 7/8"

MILLIMETRE
S

406 mm

508 mm

CAN: 457 mm

USA: 406 mm

137 mm

251 mm

*Refers to masonry fireplace opening.