TROUBLESHOOTING
13
Modular Service Tool SD
Analog Output 5 Screen
Mod Cooling Override
Analog Output #5
Override Volts: -1.0
[-1.0=Auto]
Analog Output 6 Screen
RA Damper Override
Analog Output #6
Override Volts: -1.0
[-1.0=Auto]
Analog Output 7 Screen
RA Bypass Override
Analog Output #7
Override Volts: -1.0
[-1.0=Auto]
VCB-X & VCC-X Controllers
Main Fan VFD Override Screen
Main Fan VFD
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0 volts. Voltages between
0 to 10.0 can be set for any of the Analog Output Overrides. Press
after making a setting change and the next Analog Output
Override Screen will be displayed.
Economizer Override Screen
Economizer
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press
after making a setting change and
the next Analog Output Override Screen will be displayed.
Modulating Heat Override Screen
Modulating Heat
Override Volts: -1.0
[-1.0 = Auto]
Outputs Force
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press
after making a setting change and
the next Analog Output Override Screen will be displayed.
Exhaust Fan Override Screen
Exhaust Fan Signal
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set. Press
after making a setting change and
the next Analog Output Override Screen will be displayed.
Modulating Cool Override Screen
Modulating Cool
Override %...: -10%
[-10 = Auto]
The default setting for normal operation is -10 percent. Percentages
between 0 to 100 can be set. Press
after making a setting
change and the next Analog Output Override Screen will be displayed.
Modulating Condenser 1 & 2 Override Screens
(VCB-X Only)
Mod. Condenser 1 & 2
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.
Return Air Bypass Override Screen
Return Air Bypass
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.
Return Air Damper Override Screen
Return Air Damper
Override Volts: -1.0
[-1.0 = Auto]
The default setting for normal operation is -1.0. Voltages between 0.0
and 10.0 can be set.