D-100-P1 Flow Display Manual 05/14 - 0660-3 / 18343
Page 5
SECTION 1: INTRODUCTION
1.1 PURPOSE OF THIS GUIDE
The purpose of this guide is to provide installation and commissioning procedures and basic
operating and servicing instructions for the ONICON D-100-P1 network interface.
1.2 TYPICAL D-100 NETWORK INTERFACE MODULE
The D-100 is a totalizing display module that provides a local indication of liquid, gas or steam
flow rate and total data. It can also be provided with an optional Siemens P1 RS485 network
interface to communicate data to the building control network.
D-100
SCROLL RESET PROGRAM
ONICON
3864
Steam
Building
Domestic Water Supply
Flow rate and total data to
Data Acquisition System or
Building Control System
120VAC or 24VAC
Input Voltage
1.3 SPECIFICATIONS
SIEMENS P1 NETWORK INTERFACE
Transceiver:
2-wire, half duplex
MAC address (device address) range: 1-99, (default: 017)
Baud rate:
4800
Termination:
None