beautypg.com

ONICON D-100 LonWorks User Manual

Page 14

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-LON Network Interface Installation Guide 05/14 - 0658-4 / 18342

Page 14

1.7.6 Rollover of Totals

The totals stored in the flow display memory will roll over to zero when the maximum

count is exceeded. When this occurs, the network totals will also roll over to zero. The

point at which the rollover occurs is a function of the displayed engineering units and

multipliers programmed into the display.

The examples below show the rollover point in the engineering units transmitted by the

network variable (SNVT) for common totals shown on the D-100 Flow Display.

VOLUME TOTAL

D-100 Display

Engineering Units

D-100 Display

Multiplier

LonWorks SNVT and

Transmitted

Engineering Units

Maximum Total Transmitted

Over the Network

Gallons

X 100

SNVT_vol_f – Liters

3,785,411,621 Liters

Liters

X 1000

SNVT_vol_f – Liters

9,999,999,000 Liters

X 1

SNVT_vol_f – Liters

9,999,999,000 Liters