ONICON D-100 LonWorks User Manual
Page 11
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
D-100-LON Network Interface Installation Guide 05/14 - 0658-4 / 18342
Page 11
Floating Point Output Network Variables
Description
Variable Name
SNVT Name
Engineering Units
Valid Range
Flow (volume) rate
nvoVolRateLf
SNVT_flow_f
Liters/Sec
0 to 10
12
Flow (volume) total -1
nvoVol1Lf
SNVT_vol_f
Liters
0 to 10
12
Flow (volume) total -2
nvoVol2Lf
SNVT_vol_f
Liters
0 to 10
12
*Supply temperature
nvoSupplyTempf
SNVT_temp_f
° C
-17.778 to 148.889
*Return temperature
nvoReturnTempf
SNVT_temp_f
° C
-17.778 to 148.889
*Energy rate
nvoEnrRateWf
SNVT_power_f
Watts
0 to 10
12
*Displayed energy rate
nvoDispEnrRatef
SNVT_count_f
*See note
0 to 10
12
*Energy total -1
nvoBTU1f
SNVT_BTU_f
Btu
0 to 10
12
*Displayed energy total-1
nvoDispEnergy1f
SNVT_count_f
*See note
0 to 10
12
*Energy total-2
nvoBTU2f
SNVT_BTU_f
Btu
0 to 10
12
*Displayed energy total-2
nvoDispEnergy2f
SNVT_count_f
*See note
0 to 10
12
Auxiliary pulse input (Di3) nvoAuxIn1
SNVT_count_f
None
0 to 10
12
*These network variables are present but not used by the standard D-100. The present
value for these variables will be zero.
The ASCII character status output network variables are described in the table below.
Column 1 contains a brief description of the network variables. Column 2 contains the
network variable names. Column 3 contains the Lon SNVT used for each variable.
Column 4 contains the ASCII single characters that may be transmitted by the meter
along with a description of what they indicate.
ASCII Status Output Network Variables
Description
Variable Name
SNVT Name
Valid ASCII Characters*
Meter operating
mode indicator
nvoMeterMode SNVT_char_ascii
S = Single mode (83)
D = Dual mode (68)
B = Bidirectional mode (66)
Mode status indi-
cator
nvoModeStatus SNVT_char_ascii
N = Communication lost (78)
Z = Communication restored waiting for update (90)
H = Heating mode (mode 1) (72)
C = Cooling mode (mode 2) (67)
F = Forward flow (mode 1) (70)
R = Reverse flow (mode 2) (82)
* Systems that are not set to decode ASCII characters will display the decimal equivalent.
These values are shown in parentheses.
1.7.2 Integer Format Output Network Variables
ONICON provides rate and total data to the network in integer format for systems that
cannot accept the floating point data. Refer to Appendices 3 and 4 for information on the
use of integer format SNVTs.