ONICON F-3100 MOD User Manual
Page 12

11451 Belcher Road South, Largo, FL 33773 • USA
•
Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3100-MOD Flow Meter Network Interface Installation Guide 05/14 - 0725-1
Page 12
SECTION 3: NETWORK TROUBLESHOOTING TIPS
3.1 TROUBLESHOOTING
REPORTED PROBLEM
POSSIBLE SOLUTIONS
Device will not communicate
with the network controller.
• A unique address is required for each device on the network.
Duplicate addresses will cause some or all of the devices on
the network to quit working. (See section 1.6.1 of this manual
for details.)
• The RS485 network cable connections are polarity sensitive
and must be connected the same way on every device (i.e. +
to + and - to -). (See section 1.5 of this manual for details.)
• The Baud rate setting must match the network Baud rate. (See
section 1.6.1 of this manual for details.)
• Shield drain connections should be daisy chained in the
same manner as the signal cables for RS485. The shield drain
wire should be left unterminated at the end of the cable and
connected to earth only at the network master controller.
Shield wires must not be connected to the the F-3100.
• The maximum number of devices allowed on a RS485
network segment without a repeater is 32. Adding more than
32 devices to a single segment may reduce the transceiver
output voltage to a level that is too low to be distinguished
from background noise on the cable.
• RS485 cable impedance should be matched to a termination
resistor at the end of the cable. This resistor should only be
used if the meter is the last device on the network cable. (See
section 1.6.2 of this manual for details.)
Network communications are
disrupted when the device is
connected.
• The RS485 network cable connections are polarity sensitive
and must be connected the same way on every device (i.e. +
to + and - to -). (See section 1.5 of this manual for details.)
• A unique address is required for each device on the network.
Duplicate addresses will cause some or all of the devices on
the network to quit working. (See section 1.6.1 of this manual
for details.)
• Shield drain connections should be daisy chained in the
same manner as the signal cables for RS485. The shield drain
wire should be left unterminated at the end of the cable and
connected to earth only at the network master controller.
Shield wires must not be connected to the F-3100.