F-3100-MOD Flow Meter Network Interface Installation Guide 05/14 - 0725-1

Page 11

Flow Meter Operating Status Register (Address 35)

Bit#

Description

Comment

000

Coil pulse rate too fast for coil diameter

Check for programming error for coil diamter

and/or sample rate.

001

Maximum flow alarm is active

002

Minimum flow alarm is active

003

Flow rate exceeds full scale value

Change full scale setting

004

Not used

005

Noisy or open elctrode signal

Check wiring

006

Empty pipe

007

Coil open or disconnected

Check wiring

008

Alternate flow range active

009

Flow rate below low flow cut-off

Check low flow cut-off setting

010

Flow in the negative direction

011

Not used

012

Not used

013

Not used

014

Calibration cycle in progress

015

Flow simulation mode active