Flow Meter Operating Status Register (Address 35)
Bit#
Description
Comment
000
Coil pulse rate too fast for coil diameter
Check for programming error for coil diamter
and/or sample rate.
001
Maximum flow alarm is active
002
Minimum flow alarm is active
003
Flow rate exceeds full scale value
Change full scale setting
004
Not used
005
Noisy or open elctrode signal
Check wiring
006
Empty pipe
007
Coil open or disconnected
Check wiring
008
Alternate flow range active
009
Flow rate below low flow cut-off
Check low flow cut-off setting
010
Flow in the negative direction
011
Not used
012
Not used
013
Not used
014
Calibration cycle in progress
015
Flow simulation mode active