ONICON System-10 N2 User Manual
Page 17
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322
Page 17
2.1.4 SAMPLE .ddl FILES
Single Mode Meter .ddl File
SAMPLE SINGLE MODE .ddl FILE
*****************************************************************
* ONICON, SYSTEM-10 BTU Meter: SERIAL NUMBER: XXXX
* PROGRAM VERSION: X.X
* Metasys-N2 Address: xxxx
* Single Mode
* This .ddl file is device specific to the above serial number.
*.This data is valid at the time of creation (07/23/2004 1:00 pm)
* And can be rendered invalid due to field changes in units
* or multipliers.
*
@MODEL+
CSMODEL “ONICON”,”VND”
*
AITITLE “Analog Inputs”
BITITLE “Binary Inputs”
ADTITLE “Analog Data Points”
BOTITLE “Binary Outputs”
*
ANALOG INPUTS COS AVAILABLE.
CSAI “AI1”,N,N,”ENRATE”,”10KBTU/HR”
CSAI “AI2”,N,N,”VORATE”,”10GPM”
CSAI “AI3”,N,N,”TMPSPLY”,”DEGF”
CSAI “AI4”,N,N,”TMPRTN”,”DEGF”
*
* BINARY INPUT COS AVAILABLE.
CSBI “BI1”,Y,Y, “MODEIND”,”N/A”
*
* N2 READS ADF1, ADF2 FOR ENERGY AND VOLUME TOTALS.
CSAD “ADF1”,N,N,”ENERTOT”,”10KBTU”
CSAD “ADF2”,N,N,”VOLMTOT”,”10GAL”
CSAD “ADF5”,N,N,”CNTSTOT”,”PLSSUM”
*
* NEVER MAP OUTPUT POINTS IN A CS MODEL AS DISCRETE OBJECTS.
* RESET VOLUME AND ENERGY TOTALS WITH COMMAND OVERRIDE BO ON
CSBO “BO1”,Y,Y, “RSTENTOT”,”N/A”,”reset”
CSBO “BO2”,Y,Y, “RSTVLTOT”,”N/A”,”reset”
CSBO “BO5”,Y,Y,”RSTAXTOT”,”N/A”,”reset”
****************END SINGLE MODE DDLFILE***************************