ONICON System-10 N2 User Manual
Page 13
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-N2 BTU Meter Installation and Operation Guide 05/14 - 0655-5 / 18322
Page 13
NPT
1
NPA
2
UNITS
POINT DESCRIPTION
RANGE/VALUE
BO
2
None
Reset (Zero)
Volume Total, ADF-2
OVERRIDE
Binary Output,
Object 2 - ON
BO
5
None
Rest (Zero)
Auxiliary Pulse Sum (Di3)
OVERRIDE
Binary Output,
Object 5 - ON
Note 1: Network Point Type Note 2: Network Point Address
2.1.2 Dual or Bi-Directional Mode Point Information
In either dual or bi-directional operation, two registers are available for the accumulation
of energy and two are available for the accumulation of volume. Thus, four ADF points are
required. Four binary output points are required to zero the four ADF energy and volume
accumulation registers.
NPT
1
NPA
2
UNITS
POINT DESCRIPTION
RANGE / VALUE
AI
1
Selectable
(See Energy Rate Table)
Energy Rate
0 – 999,999
AI
2
Selectable
(See Volume Rate Table)
Volume Rate
0 – 999,999
AI
3
Deg F
Supply Temperature
0.0 Deg F – 250.0 Deg F
AI
4
Deg F
Return Temperature
0.0 Deg F – 250.0 Deg F
BI
1
None
Heating – Cooling Indicator
0 – Heating; 1 - Cooling
ADF
1
Selectable
(See Energy Total Table)
Mode 1 Energy Total
0 – 999,999
ADF
2
Selectable
(See Volume Total Table)
Mode 1 Volume Total
0 – 999,999
ADF
3
Selectable
(See Energy Total Table)
Mode 2 Energy Total
0 – 999,999
ADF
4
Selectable
(See Volume Total Table)
Mode 2 Volume Total
0 – 999,999
ADF
5
User Defined
Auxiliary Pulse Input Sum
(Di3)
0 – 999,999
BO
1
None
Reset Mode 1 Energy Total
OVERRIDE
Binary Output,
Object 1 - ON
BO
2
None
Reset Mode 1 Volume Total
OVERRIDE
Binary Output,
Object 2 - ON
BO
3
None
Reset Mode 2 Energy Total
OVERRIDE
Binary Output,
Object 3 - ON