SECTION 3: NETWORK TROUBLESHOOTING TIPS

3.1 TROUBLESHOOTING

REPORTED PROBLEM

POSSIBLE SOLUTIONS

Device will not

communicate with the

network controller.

• Is the Transmit LED on the display flashing? The Transmit LED

will only flash when the device is responding to a poll. A unique

address is required for each device on the network. Duplicate

addresses will cause some or all of the devices on the network to

quit working. (See section 1.6.1 of this manual for details.)

• The RS485 network cable connections are polarity sensitive and

must be connected the same way on every device (i.e. + to + and -

to -). (See section 1.4 of this manual for details.)

• The Baud rate setting must match the network Baud rate. (See

section 1.5.1 of this manual for details.)

• Shield drain connections should be daisy chained in the same

manner as the signal cables for RS485. The shield drain wire

should be left unterminated at the end of the cable and connected

to earth only at the network master controller. Shield wires must

not be connected to the RS485 connector on the F-5100.

• The maximum number of devices allowed on a RS485 network

segment without a repeater is 32. Adding more than 32 devices to a

single segment may reduce the transceiver output voltage to a level

that is too low to be distinguished from background noise on the

cable.

• RS485 cable impedance should be matched to a termination

resistor at the end of the cable. This resistor should only be used if

the meter is the last device on the network cable. (See section 1.5.2

of this manual for details.)

Network communications

are disrupted when the

device is connected.

• The RS485 network cable connections are polarity sensitive and

must be connected the same way on every device (i.e. + to + and -

to -). (See section 1.4 of this manual for details.)

• Is the transmit LED flashing? The transmit LED will only flash

when the device is responding to a poll. A unique address is

required for each device on the network. Duplicate addresses will

cause some or all of the devices on the network to quit working.

(See section 1.6.1 of this manual for details.)

• Shield drain connections should be daisy chained in the same

manner as the signal cables for RS485. The shield drain wire

should be left unterminated at the end of the cable and connected

to earth only at the network master controller. Shield wires must

not be connected to the RS485 connector on the F-5100.