ONICON F-5100 MOD Network User Manual
Page 12
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-5100-MOD Flow Meter Network Interface Installation Guide 05/14 - 0669-6
Page 12
REGISTER
ADDRESS
DESCRIPTION
REGISTER TYPE
READ / WRITE
COMMENT
313
Flow Total - part 1
Long Integer (1 of 2)
Read / Write
Write 0 to reset
total.
314
Flow Total - part 2
Long Integer (2 of 2)
Read / Write
REGISTER
ADDRESS
DESCRIPTION
REGISTER TYPE
READ / WRITE
COMMENT
579
Flow Rate - part 1
Floating Point (1 of 2)
Read Only
580
Flow Rate - part 2
Floating Point (2 of 2)
Read Only
581
Temperature - part 1
Floating Point (1 of 2)
Read Only
582
Temperature - part 2
Floating Point (2 of 2)
Read Only
583
Zero Cal. - part 1
Floating Point (1 of 2)
Read Only
584
Zero Cal. - part 2
Floating Point (2 of 2)
Read Only
REGISTER
ADDRESS
DESCRIPTION
REGISTER TYPE
READ / WRITE
COMMENT
835
Flow Rate - part 1
Scaled Long Integer (1 of 2)
Read Only
Multiply long
integer by .001 to
read value.
836
Flow Rate - part 2
Scaled Long Integer (2 of 2)
Read Only
837
Temperature - part 1
Scaled Long Integer (1 of 2)
Read Only
838
Temperature - part 2
Scaled Long Integer (2 of 2)
Read Only
839
Zero Cal. - part 1
Scaled Long Integer (1 of 2)
Read Only
840
Zero Cal. - part 2
Scaled Long Integer (2 of 2)
Read Only