Step 2 – wiring the nortec links 2 module – Nortec LINKS 2 SETC B+ User Manual
Page 17

13 | Links 2 Retrofit for GSTC / SETC B+, NHTC, NHRS
Step 2 – Wiring the Nortec Links 2 Module
1 Most of the wiring connections for the new Nortec LINKS 2 module will have already been
finished at the factory; however, there is an additional Logic Card that must be installed.
Refer the LINKs 2 wiring diagram included in the package for added details.
2 Module Power Connections: There will be a wire harness provided that will consist of a red
and blue wire. Both red and blue wires are terminated ring terminals. Cut the terminals off
and strip off 1/8” insulation on the end.
a The red wire is to be connected to the left side of contact #1 (24v) on the main terminal strip.
The blue wire is to be connected to the left side of contact #3 (ground) on the main terminal
strip.
Figure 16: Humidifier Man Terminal Strip