3 | HP Series Installation Manual

After unpacking, inspect equipment for damage and if damage is found, notify the shipper

promptly.

All Nortec products are shipped on an F.O.B. factory basis. Any and all damage, breakage or
loss claims are to be made directly to the shipping company.

Absorption Distances

An important consideration in the planning of a HP HVAC system is the absorption distance, or
the distance it takes for the droplets to evaporate inside the HVAC system. The absorption
distance is relative to the air velocity, temperature, atmospheric pressure, and the amount of
water in the incoming air. In applications where space is limited, such as in an air-handler,
precautions should be taken to prevent the wetting of sensitive components downstream.

Components

Nortec Supplied

Nortec will supply the following components:

1 High pressure pump skid
2 Valve controller
3 Valve block assembly
4 Nozzle manifolds
5 In-duct plumbing
6 Mist eliminator (optional)
7 Air proving switch (optional)
8 High limit humidistat (optional)
9 Humidistat (optional)
10 Reverse osmosis system (optional)

Field Supplied

The Installer is responsible for supplying the following:

1 Electrical disconnects
2 All electrical wiring
3 Piping from the RO system to pump module
4 High pressure piping between pump and manifolds
5 Flex hose
6 P-traps
7 Drain funnels
8 Wet duct section (drain pans, wall sections, sealants, fasteners)
9 Pump skid vibration dampening
10 Electricity, water, and airflow