4 | AirFog Installation Manual
Parts
A parts list should be included with the drawings developed by the designer. Not all the
necessary parts are provided by Nortec. The following parts are supplied by others:
Pipe, elbows, pipe hanger and mounting hardware for inside HVAC units, T-joints, pipe size
adapters, Teflon sealing tape and other plumbing supplies from a local plumbing supplier.
Pipe material is either copper, stainless steel or plastic and should be specified on the
designer produced drawings.
Wire for the electrical connections is 18 gauge standard insulation, which can carry 24 Volts
AC at 1 amp. This wire can be purchased from most electrical suppliers.
Nails, screws, bolts, threaded rods, anchors, rivets etc. to attach mounting brackets to the
structure. The fasteners used will depend on the material used in the mounting surface.
Insulation for the cold water pipe feeding the system is required to prevent water vapor from
condensing and dripping on other structures, machines, personnel or materials.
The Nortec supplied parts should be checked against the designer’s drawings and parts list
to ensure the correct quantity of the correct part numbers are available.