beautypg.com

Nortec Steam Distribution User Manual

Page 7

background image

Steam Line Distribution Installation Manual | 4

Condensate Return Guidelines for Main Steam Lines

Use vertical condensate leg of distributor only. Do not over-tighten clamp.

Condensate traps on steam mains must be located at all low points in the system, at each

elevation change and or directional change.

Horizontal runs of steam must rise 2” per foot (10°) when flow is going upwards away from

condensate trap, and fall ½” per foot (2°) when flow is going downwards towards a condensate

trap.

In a horizontal run of the steam main, condensate traps must be located at regular intervals of 20

feet.

The condensate trap itself is a section of piping connected to the bottom of the main. A full size tee

must be used to create a condensate trap to allow the condensate to fall away from the steam

flow.

Vertical drop of the condensate trap should be 1.5 times the diameter of the steam main but no

less than 12”.

A P-trap should be installed at the bottom of the condensate trap. The center to center trap height

should be 2” greater than duct static pressure.

All distributors must be individually trapped.



Figure 1: Drain Tee