6. Specifications

MODEL

6000U

10000U

CAPACITY*

6000 VA / 5400 W

10000 VA / 9000 W

INPUT

Voltage
Range

Low Line Loss

110 VAC ± 3 % at 50% Load;

176 VAC ± 3 % at 100% Load

Low Line Comeback

Low Line Loss Voltage + 10V

High Line Loss

300 VAC ± 3 %

High Line Comeback

High Line Loss Voltage - 10V

Frequency Range

46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system

Phase

Single phase with ground

Power Factor

0.99 at 100% Load

OUTPUT
Output voltage

200V/208/220/230/240VAC

AC Voltage Regulation

± 1%

Frequency Range

(Synchronized Range)

46Hz ~ 54 Hz @ 50Hz system

56Hz ~ 64 Hz @ 60Hz system

Frequency Range (Battery Mode)

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz

Overload

Line mode

100%~110%: 10min;

110%~130%: 1min;

>130% : 1sec

Battery mode

100%~110%: 30sec;

110%~130%: 10sec;

>130% : 1sec

Current Crest Ratio

3:1 max

Harmonic Distortion

2 % @ 100% Linear Load;

4 % @ 100% Non-linear Load

Transfer

Time

Line

Battery

0 ms

Inverter

Bypass

0 ms

Inverter

ECO

<10 ms

EFFICIENCY
Line mode

> 90%

Battery Mode

> 88%

BATTERY

Standard

Model

Type & Numbers

12 V / 7 Ah x 20

12 V / 9 Ah x 20

Recharge Time

7 hours recover to 90% capacity

9 hours recover to 90% capacity

Charging Current

1 A ± 10% (max.)

Charging Voltage

273 V ± 1%

Long Run
Model

Type

Depending on applications

Numbers**

18 – 20

Charging Current

4 A ± 10% (max.)

Charging Voltage

273 V ± 1%

PHYSICAL

Dimension,DXWXH(mm)

UPS unit: 580X438 X133

Battery pack: 580X438 X133

UPS unit: 668X438 X133

Battery pack: 580X438 X133

Net Weight (kgs)

UPS unit: 20

Battery pack: 57

UPS unit: 23.5

Battery pack: 63

ENVIRONMENT
Operation Temperature

0 ~ 40°C (the battery life will down when > 25°C)

Operation Humidity

<95 % and non-condensing

Operation Altitude***

<1000m

Acoustic Noise Level

Less than 58dB @ 1 Meter

Less than 60dB @ 1 Meter

MANAGEMENT
Smart RS-232 or USB

Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC

Optional SNMP

Power management from SNMP manager and web browser

* If the UPS is in converter mode, the power capacity will be derated to 60% of full capacity;
**If the battery number is 18, the power capacity will be derated to 90%; if it is 19, the power capacity will be derated to 95%;

***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.

Product specifications are subject to change without further notice.