Fault

04: Bus Unbalance

1) The load is special or abnormal,

so the internal positive and

negative DC bus voltages are

unbalanced.

2) The internal converter failed.

Contact the dealer.

Fault

11: Inv Start Fail

The internal inverter failed, so the

inverter voltage could not start up

correctly.

Contact the dealer to repair.

Fault

12: Inv Volt High

The internal inverter failed, so the

inverter voltage is too high.

Contact the dealer to repair.

Fault

13: Inv Volt Low

The internal inverter failed, so the

inverter voltage is too low.

Contact the dealer to repair.

Fault

14: Output Short

Short circuit occurs on the UPS

output.

Remove short circuit.

Fault

1A: NegPower

UPS output power is negative. It

means there is energy feedback

into the internal of UPS from

output. It may be caused by

regenerative load or current control

failure in the parallel system.

Contact the dealer.

Fault

21: Batt SCR Short The internal battery SCR is failed

and short.

Contact the dealer to repair.

Fault

24: Inv Rly Short

The internal inverter relay is stick to

short or the SCR of STS (Static

Transfer Switch) is short.

Contact the dealer to repair.

Fault

35: Para Comm Fail

Parallel cable for communication is

not connected well in the parallel

system.

Connect the parallel cable well.

Fault

36: OP.I Unbalance

The output current is extremely

unbalanced between the paralleled

UPSs or there is an error in the

parallel system.

Contact the dealer to repair.

Fault

41: Over Temp

The internal temperature is too

high and reach the fault level

(shutdown):

1) Maybe the environment is hot.

2) Maybe the fan is blocked or

failed.

3) Maybe ventilation is blocked by

the wall or other goods.

4) Load is too heavy.

1) Make sure the ambient

temperature not over 40ºC.

2) Make sure the fan is OK.

3) Make sure ventilation is well.

4) Remove some loads if

possible.

Fault

42: CPU Comm Fail

Internal communication failure

between CPUs.

Contact the dealer to repair.

Fault

43: Over load

Overload time is out of the

specification and the UPS shuts
down automatically.

Remove excess loads from UPS

output and restart it.