beautypg.com

Niveo Professional NUPS22-6000U User Manual

Page 28

background image

Warning

0D: Over Temp

The internal temperature is too

high and reach the warning level:

1) Maybe the environment is hot;

2) Maybe the fan is blocked or

failed;

3) Maybe ventilation is blocked by

the wall or other goods.

4) Load is too heavy.

1) Make

sure

ambient

temperature not over 40ºC.

2) Make sure the fan is OK.

3) Make sure ventilation is well.

4) Remove some loads if

possible.

Warning

0E: Charger Fail

Charger failed.

Contact the dealer for repair.

Warning

10: IP Fuse Open

Input fuse on the power stage

board is burnt.

Check and replace the input

fuse.

Warning

33: Overload 3Times Locked in bypass after overload 3

times in 30 minutes.

Remove excess loads from UPS

output first. Then, shut down

the UPS and restart it.

Warning

3A: Maintain Open

EMBS port is open or the maintain

switch sensor (connected to EMBS
port) is trigged. (The UPS is

transferred to bypass).

If

the

EMBS

port

is

short-circuited, the warning will
disappear.

Warning

3F: Para Protect

Parallel cable is still not connected

well when restart after the parallel

system is fault because of parallel

communication failure. (When this

warning appeared, the UPS could

not start up because it is system

protection for parallel system)

1) If the system is still needed

to be operated in parallel

mode, please connect the

parallel cable well. And,

choose “Para Unlock” in

control menu to remove the

warning. Then, the UPS

could start up.

2) If the UPSs in the system are

separated to single UPS,

please disconnect the output

to other UPSs and choose

“Para Unlock” in control

menu to remove the

warning. Then, the UPS

could start up.

NOTE: Be careful to check

the UPS operation mode

(parallel or single) and the

connections. If the parallel

cable is not connected in the

parallel mode, the UPS may

be damaged.

Fault

01: Bus Start Fail

The internal converter failed, so the

DC bus voltage could not be

boosted correctly.

Contact the dealer to repair.

Fault

02: Bus Over

1) DC bus voltage is too high

because of mains input or load

transient current.

2) The internal converter failed.

1) Shut down and restart the

system to see if it happens

again.

2) Contact the dealer to repair.

Fault

03: Bus Under

The internal converter failed, so the

DC bus voltage is too low.

Contact the dealer to repair.

This manual is related to the following products: