5) Calibration

Interface

Description

1. Batt: Calibrate the battery voltage measurement. Calibration

range is from 0V to 5.7V. The default value is 0V. It is available on

all operation modes.

2. Inv: Adjust the inverter output voltage; the adjustable range is

from 0V to 6.4V, the default value is 0V. It is only available in line

/ battery / converter mode;

3. Chg: Adjust the Charger output voltage; the adjustable value is

from 0V to 6.9V, the default value is 0V. It is only available in

bypass / line / ECO /converter mode.

(NOTE: Before making charger output voltage adjustment, be

sure to disconnect all batteries first to get the accurate charger

voltage; Be careful that the adjustment should be suitable to

battery specifications, or the battery maybe destroyed.)

6) Other settings (available on all operation modes)

Interface

Description


Hot standby:

Enable: Hot standby function is enabled. It means that the current

UPS is set to be host of hot standby system, and it will automatically

restart after AC recovery even without battery connected.

Disable: Hot standby function is disabled. The UPS is running at

normal mode and can’t restart without battery.

Disable is default setting.