Hose installation – MovinCool Condensate Pump User Manual
Page 9

Note: Please check the drainage
performance after installation. It
is important that the drainage line
from the pump is free of kinks and
is not pinched.
Power fluctuation or low voltage
could result in incorrect drainage.
To ensure proper drainage,
locate the highest vertical posi-
tion, no more than the maximum head lift which shown in the table
below, and run the drain hose on a downward slope at a minimum
rate of 1/4 inch(6.25mm) per foot .
HOSE INSTALLATION
For Office Pro 36 Only
Connect the remainder of the 20
foot (6 m) hose to the drain outlet
spout and feed it through the
grommet on the right hand side of
the unit.
DRAIN HOSE
DRAIN STEM
DRAIN HOLE
DRAIN HOSE
Maximum head lift
115V Pump
230V Pump
230VAC
208VAC
20 feet (6m)
17 feet (5.2m)
13 feet (4m)
DRAIN HOSE
1/4" TAPER
PER FOOT
CONDENSATE
PUMP
Le
ss
th
an
M
ax
im
um h
ea
d
lif
t
9