MAINTENANCE & TROUBLESHOOTING
! WARNING: When performing any maintenance and/or troubleshoot-
ing, make sure that all electrical power is off. This means before service,
unplug the unit from the electrical outlet or if permanently wired, make
sure the circuit breaker is in the off position.
1) Remove any dirt or debris which may collect in the bottom of the
reservoir tank.
2) On a monthly basis, check the condensate drain hose for kinks,
blockage or any other damage that may obstruct condensate pump
from draining properly.
3) Always replace the fan motor cover to keep electrical parts free of
dust, dirt and any other foreign material.
Drain Tank Overflow Switch
This safety feature will stop the compressor operation if the pump
malfunctions. To test the drain tank overflow switch, pinch the drain outlet
hose and pour water into the reservoir inlet drain hole. Continue to fill
the reservoir until the rising water lifts the overflow switch and stops the
operation.
Note: If the Fan Mode Control DIP Switch is set to the “STOP”
position, the entire unit (including fan operation) will turn off.
If the compressor continues to operate when the reservoir is full, check
your installation procedure. After testing is complete, release the drain
outlet hose and the condensate pump will empty the reservoir. Make sure
the 9 in(23cm) section of hose is installed into the inlet drain hole of the
pump reservoir.
Condensate Pump
3/8" I.D. DRAI N
OUTLET SPOUT
WITH CHECK VALVE
MOTOR FAN
COVER
RESERVOIR
DRAIN TANK OVERFLOW
SWITCH FLOAT
MAIN CONTROL
FLOAT
MOUNTING EAR
1" INLE T
DRAIN HOLE