Flexible lamp – Delta 23-735 User Manual
Page 10
10
Fig. 17
A
2. Grounded, cord-connected tools intended for use on
a supply circuit having a nominal rating less than 150
volts:
This tool is intended for use on a normal 120-volt circuit
and has a grounded plug that looks like the plug
illustrated in Fig. 15.
If a properly grounded outlet is not available, a temporary
adapter, shown in Fig. 16, may be used for connecting the
3-prong grounding type plug to a 2-pole receptacle. The
temporary adapter should be used only until a properly
grounded outlet can be installed by a qualified electrician.
The green colored rigid ear, lug, or the like extending from
the adapter must be connected to a permanent ground
such as a properly grounded outlet box cover. Whenever
the adapter is used, it must be held
In place with a metal screw.
NOTE: In Canada, the use of a temporary adapter is
not permitted by the Canadian Electric Code.
WARNING: IN ALL CASES, MAKE CERTAIN
THE RECEPTACLE IN QUESTION IS PROPERLY
GROUNDED. IF YOU ARE NOT SURE HAVE A
CERTIFIED ELECTRICIAN CHECK THE RECEPTACLE.
FLEXIBLE LAMP
The flexible lamp operates independently of the grinder.
To turn the lamp on and off, rotate switch (A) Fig. 17.
WARNING: To reduce the risk of fire, use 40 watt
or less, 120 volt, reflector track type light bulb (not
supplied). A standard household light bulb should
not be used. The reflector track type light bulb
should not extend below the lampshade.
Fig. 15
GROUNDED OUTLET BOX
CURRENT
CARRYING
PRONGS
GROUNDING BLADE
IS LONGEST OF THE 3 BLADES
Fig. 16
GROUNDED OUTLET BOX
GROUNDING
MEANS
ADAPTER