beautypg.com

1 phase cliq din rail power supply, 120 w 1 phase cliq power supply, Features – Delta Electronics CliQ User Manual

Page 5: Mechanical drawings

background image

Features:

● Ease of wire connection to terminals
● Compact design for easy handling
● Overload protection
● Overvoltage protection
● Thermal protection
● Power boost 150% for 3 seconds
● Expected life time: 10 years
● Redundancy: Yes (with external oring
diode)
● RoHS compliant

DRP024V120W1AA

1 Phase CliQ DIN Rail Power Supply

MECHANICAL DESIGN

Case cover

Aluminium (Al5052)

Dimensions (L x W x H)

121 mm x 50 mm x 115 mm

Unit weight / box

0.540 kg

MTBF

> 800,000 hrs

Noise

Sound pressure level (SPL) < 40 dBA

Cooling

Convection

Input terminal

M4 x 3

Output terminal

M4 x 2 (2 pcs.)

Mounting rail

Standard TS35 mounting rail

Shock proof

IEC 60068-2-27

Vibration

IEC 60068-2-6

Protection structure

EN 60950 meet IPX0

SAFETY

EMC / Emissions

Class B / EN55022, CISPR22, Class B; FCC Tilte 47;
EN 61204-3 (Class B on AC & Class A on DC side)

Immunity

EN 61000-4-2, 1995; EN 61000-4-3, 1998; EN 61000-4-4,
1995; IEC 61000-4-5, 1995; EN 61000-4-6, 1996;
EN 61000-4-8 or IEC 61000-4-12 or IEEE C62.41;
EN 61000-3-2, 1994

Approvals

UL508, EN 60950, cULus 60950, EN 50178, EN 60204,
GS

Voltage dips

Conform to EN 61000-4-11

Galvanic isolation

Input to output: 4 KVac
Input to ground: 1.5 KVac
Output to ground: 1.5 KVac

120 W 1 Phase CliQ Power Supply

Mechanical drawings

ENVIRONMENTAL

Operating ambient temperature

-20°C ... +75°C *

Storage temperature

-25°C ... +85°C

Humidity operation

< 95%

Note (*)

* Operating amb. > 50°C derate power by 2.5% / °C

INPUT SPECIFICATIONS

Input voltage range

85 - 264 Vac (DC input range 120 - 375 Vdc)

Input frequency

47 Hz - 63 Hz

Nominal current

1.4 A @ 115 Vac, 0.8 A @ 230 Vac

Inrush current limitation l²t

(+25°C) typ.

< 80 A @ 115 Vac

Power factor

Conform to EN 61000-3-2 STD

Efficiency

> 84% typ.

Leakage current

< 1 mA

OUTPUT SPECIFICATIONS

Output power

120 W

Output voltage range

22 V - 28 V

Output current

5 A

Residual ripple / peak
switching (20 MHz)
(at nominal values)

< 50 mV / < 240 mVpp

Mains buffering at nominal
load (typ.)

> 35 ms @ 115 Vac, > 70 ms @ 230 Vac

Line regulation

< 0.5% typ. (@ 85 - 264 Vac input,
100% load)

Load regulation

< 1% typ. (with rated input, 0 - 100% load)

1 Phase 120 W CliQ DIN Rail Power Supply

The new CliQ DRP024V120W1AA is the latest offering from
one of the world‘s largest power supply manufacturers -
Delta.
The product offers a nominal output voltage of 24 V, a wide
temperature range from -20°C to +75°C and a minimum hold-
up time of 20 ms.
The state-of-the-art design is made to withstand harsh indus-
trial environments. The rugged, ultra-compact metal case is
shock and vibration resistant according to IEC 60068-2.
The 120 watts CliQ DIN Rail power supply provides overvolt-
age, overload and thermal protection.
Due to the wide input voltage range from 85 to 264 Vac, the
Delta’s CliQ power supply is worldwide usable.
Multiple output terminals for fast wiring and easy installation.

120 W 1 Phase CliQ Power Supply

8

7

24V

5A

Adjust

DC O K

L

N

100-240V~ 2A 50-60Hz