Herrmidifier Herrtronic RDU-D User Manual

Page 8

background image

Herrtronic

®

RDU-D Supplement

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

8

www.herrmidifier-hvac.com

VII. TROUBLESHOOTING

Problem/Symptom

Reason / Correction

Steam Condensing on RDU sheetmetal or other objects. 1. Adjust louvers per figure 12

2. Fan not running. Check pressure switch for fail closed

condition. Herrtronic unit should not operate if fan is not

running.

3. Too little airflow. Increase fan speed.

4. Room is very cold, very humid, or objects are cold.

Decrease humidity setpoint at Herrtronic unit or humidity

controller.

Fan not energizing

1. Check that the fan rotates freely.

2. Check fuses in RDU.

3. Check wiring to fan.

4. Check voltage to fan - should be 220 VAC +/- 10%.

5. Replace fan and capacitor.

Fan speed adjustment not working.

1. Replace rheostat.

Water spitting out of manifold

1. Check condensate drain hose. If it is clogged, clean.

2. Make sure condensate drain hose is sloped properly

and there are no low spots or kinks.

Fan does not continue to operate for 15 minutes after

Herrtronic unit shuts down.

1. Check wiring to relay/timer.

2. Check that the 24 VAC is present between terminal #2

and #3 on relay timer. If so, replace timer.

Air pressure switch not closing.

1. Fan speed setting too low. Increase fan speed.

2. Check tubing on switch for clogging or out of position.

3. Faulty air pressure switch. Replace.

Blown fuses in RDU

1. Check fan for short circuit.

2. Check RDU wiring for short circuit.