beautypg.com

Herrmidifier Herrtronic RDU-D User Manual

Page 6

background image

Herrtronic

®

RDU-D Supplement

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

6

www.herrmidifier-hvac.com

V. REMOTE MOUNT OPTION (MDM, MDS, MDD)

1. The RDU may hang directly on a wall using the two

1/4” x 2” lag screws included. There are two key-hole

slots on the back of the cabinet which engage these

screws. Be certain that: 1) the screws are fastened

securely enough to the wall to support the 40 lbs.

weight of each RDU unit, and 2) the screws are level.

Turn the screws in until the heads are 1/8” away from

the mounting surface.

2. Hang the unit on the wall and tighten the two lag

screws.

3. The steam hose(s) is to be connected using the steam

inlet union(s) (Figure 8).

4. Trim the steam hose(s) which is connected to the RDU

manifold so that it fits properly onto the union(s) and

secure connections with a hose clamp(s).

5. Fasten steam inlet union(s) to bottom or back of RDU

cabinet with screws.

6. Remove the knockout from the top of the Herrtronic

cabinet and install the 5/16” I.D. plastic bushing

(included).

7. Remove the 18” piece of condensate return tubing

connected to the manifold elbow.

8. Uncoil the 10’ piece of condensate return tubing (drain

line), feed into the RDU cabinet, from the bottom or

back, and connect to the manifold elbow.

9. Run the condensate return tubing down into the

Herrtronic cabinet through the 5/16” I.D. plastic

bushing.

10. The condensate tubing can be attached to the steam

hose or electrical conduit interconnecting the RDU

and Herrtronic with cable ties or equivalent.

11. After the condensate tubing is secured, insuring that

there are no kinks or low spots, the length should be

trimmed so that it can extend 1” into the grey plastic fill

tee in the Herrtronic unit.

12. National, state or local electrical codes may require

the use of two separate conduits - one for high voltage

supply power and one for control wiring.

13. There are a total of seven wires which are to be

connected between the RDU and the Herrtronic unit.

The RDU receives all of its power and control from the

Herrtronic unit. Use the two 7/8” holes or knockouts

on the bottom or back of the RDU cabinet and the two

7/8” knockouts on the top of the Herrtronic cabinet for

wiring conduit.

14. Wires #3 and #4 are the high voltage power supply

and should be run in one conduit.

15. Along with the ground wire #24, wires #1, #2, #5, and

#6 should be run in the second conduit.

16. Connect wires # 1-6 to the 6 pole RDU terminal strip

located near the top of the Herrtronic high voltage

electrical compartment. Connect the ground wire #24

to the Herrtronic ground terminal located near the

bottom of the high voltage compartment.

NOTE

See Figure 15, 16 & 17 for standard electrical hookup

for MDM and MDS.

17. Remove jumper wire #39 from the Herrtronic 12

pole controls terminal strip located in the low voltage

electrical compartment between poles #1 and #2.

18. Replace the RDU cover and the fan speed control

knob.

Installation is now complete. Proceed to the RDU operation

section then to the start-up section of the Herrtronic

Installation, Operations and Service Manual OM-93.

Figure 8 - Steam Connections (Side View)

Figure 9 - Drain Line (Front View)

Figure 10 - MDS Remote Mount

BLOWER

DRAIN

LINE

STEAM HOSE

STEAM INLET UNION

(REMOTE MOUNT)

STEAM INLET UNION
(ALTERNATE LOCATION)

DRAIN

LINE

GRILL

>50 lb/hr requires second hose

CYL FULL

POWER

FAULT

BACK

ON/OFF

FAULTS

ENTER

HERRTRONIC MD

Figure 10 - Front View