Herrmidifier Herrtronic RDU-D User Manual

Page 3

background image

Herrtronic

®

RDU-D Supplement

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

3

www.herrmidifier-hvac.com

I. LIMITED WARRANTY

Seller warrants the equipment of its manufacturing to

be free from defects in workmanship and material for a

period of 24 months after shipment. This warranty is

limited, however, to the repair or replacement of defective

equipment, which is returned, freight prepaid, to Seller’s

factory.

This limited warranty does not apply to any part or

component that is damaged in transit or when handling,

has been subject to misuse, negligence or accident, has

not been installed, operated or serviced according to

Seller’s instructions, or has been operated beyond the

factory-rated capacity or has been altered in any way.

Seller’s liability is limited to replacement of defective parts

or components and does not include any cost of labor

(including, but not limited to, labor required to remove and/

or reinstall any defective part) other than Trion/Herrmidifier

factory labor.

Trion/Herrmidifier shall not be responsible for loss of use

of any product, loss of time, inconvenience, or damage

to other equipment, or any other indirect or consequential

damage with respect to property whether as a result of

breach of warranty, neglect, or otherwise.

THE WARRANTIES AND LIABILITIES SET FORTH ARE

IN LIEU OF ALL OTHER WARRANTIES AND

LIABILITIES, EXPRESSED OR IMPLIED, IN LAW OR

IN FACT, INCLUDING IMPLIED WARRANTIES OF

MERCHANTABILITY AND FITNESS FORPARTICULAR

PURPOSE.

The foregoing shall constitute the total liability of seller

in the case of defective performance of all or any of the

equipment or services provided to Buyer. Buyer agrees

to accept and hereby accepts the foregoing as the sole

and exclusive remedy for any breach or alleged breach of

warranty by Seller.

II. GENERAL DESCRIPTION

The RDU-D Series Room Distribution Units are designed

as a companion module for all MD Series Herrtronic

humidifiers.

The RDU may be directly mounted on top of the Herrtronic

cabinet or mounted remotely. The RDU consists of a fan,

controls, & steam hose to distribute the steam directly into

the space. RDU-D must he remotely mounted when used

with an MDM series humidifier.

Figure 1 - Mounting Options

Model No

Electrical

Characteristics

Capacity

RDU-D-1

208-240-1-50/60

5-50 lbs/hr.

RDU-D-1T

480-600-1-50/60

RDU-D-2

208-240-1-50/60

60-100 lbs/hr.

RDU-D-2T

480-600-1-50/60

RDU-D-2R

208-240-1-50/60

110-250 lbs/hr.

RDU-D-2L

208-240-1-50/60

RDU-D-2TR

480-600-1-50/60

RDU-D-2TL

480-600-1-50/60

Note: 1T & 2T models include a transformer to provide

208/230 single phase power to the RDU.

Note: MDD Units require two RDU units. For Direct

Mount you must use a specific right and left mount unit.

For remote mount, two Identical units may be used.

For remote mounting applications, the plumbing and

electrical connections may be routed through the bottom

or back of the RDU. There are two electrical knockouts,

two steam supply knockouts and one condensate return

knockout on both the bottom and back to facilitate

installation.