Installation – Groth 7658A User Manual
Page 3

3
The flame arresters consist of two main 
components, the arrester bases and the flame 
element housing assembly. The bases serve as 
the connecting interface to the piping system. 
The housing retains and supports the flame 
element. Both components are essential in 
stopping the passage of the flame. 
The flame element is comprised of small parallel 
passageways aligned so that an approaching 
flame front is slowed down and then quenched 
before it can propagate to the protected side of 
the device. All Groth flame elements utilize 
spiral wound, crimped ribbon constructed of 
corrosion resistant materials, to insure the best 
flame quenching performance with minimum 
pressure drop. The element is supported by rigid 
beams, securely welded into the housing to 
withstand the extreme pressures of an overdriven 
detonation. Each nominal size arrester can be 
supplied with various diameter elements to 
provide the required flow capacity. 
The bases must also withstand the detonation 
pressures while conveying the burning vapors 
and flame front to the element. Depending on 
the design of the system in which it is used, the 
arrester bases can include optional ports for 
thermocouples or pressure monitoring devices. 
These devices can activate warning or shutdown 
systems if abnormal conditions are detected. 
Both bases may be equipped with large diameter 
inspection/clean-out ports for in-line 
maintenance of the element, or element removal 
may be required for inspection/maintenance. 
Note
A Type II detonation flame arrester cannot 
withstand a continuous flame, and must have 
a continuous flame monitoring system 
capable of shutting down the vapor flow 
within the time specified on the arrester 
nameplate. 
WARNING
A detonation flame arrester may be exposed 
to instantaneous pressure spikes in excess of 
1000 PSI. Any instrumentation attached to 
the arrester must be capable of continued 
operation in this environment. 
INSTALLATION
Operating Conditions:
Based on the testing conditions, this series of 
detonation flame arrester may be installed in 
piping systems where: 
1. The MESG of the vapor constituent(s) is
greater than or equal to .036" (0.92 mm).
2. System operating pressure is less than or
equal to 15.7 PSIA (1.08 Bar).
3. Normal operating temperature is between -
13
o
F (-25
o
C) and 140
o
F (60
o
C).
4. The piping system in which the detonation
arrester is to be installed must not exceed the 
arrester flange size. 
WARNING
The 7658A detonation flame arrester may NOT 
be effective in stopping flame propagation in 
systems which contain vapors with an MESG 
less than 0.036" [0.92 mm] or when any of the 
operating conditions are exceeded.
All Groth Detonation flame arresters are bi-
directional and can be used in vertical or 
horizontal piping systems. 
WARNING
The flame arrester housings or adjacent piping 
may have various pipe taps for pressure 
sensing, temperature sensing, condensate 
drainage, etc. Never connect such taps to a 
common line or system as this could provide a 
flame bypass around the flame arrester 
element. 
 
This series of flame arresters all have 150# ANSI 
flanges. Please follow the torque guidelines 
listed in Table 1 for flange make-up torque. 
 
Note
When transporting the detonation arrester, 
support it with the flanges in the horizontal 
position. This position provides the maximum 
support for the flame element winding. Lift the 
assembly with the [2] lifting eyes attached to the 
bases if applicable. 
 
