Greenheck Temperature Control Package v2.0 (461468) User Manual
Page 6

6
Unit Set-Up Loop (cont’d)
Cool Parameters
Band: 10.0F
Int: 005S
Time Off: 
300S
Cool Parameters
Band
The dead-band around the cooling set points. The smaller the 
band setting, the more sensitive the controller will be to small 
temperature changes.
Integration
The integration setting (in seconds) is the time necessary for 
the integer value to be doubled (i.e. increasing the time setting 
decreases the response time).
Time Off
For DX cooling only. The delay (in seconds) before an “On” 
signal is sent to the compressor upon initial power being 
supplied to the controller. This feature provides a safety delay 
for the compressors to prevent short-cycling during power 
interruption to the controller. This delay will be in addition to 
any time delays built into the compressor.
DX Rotation
Btwn Stages: 060S
Btwn Starts: 
300S
DX Rotation
(2-stage condensers only)
To avoid short-cycling the condensing unit, a time delay between stages and 
a time delay between starts may be set. The condensing unit may also have 
delays built-in, so ensure compatibility between the times set in the controller 
and condenser.
Btwn Stages Minimum time which must elapse between different 
compressors turning on.
Btwn Starts
 Minimum time which must elapse between a compressor 
turning off and turning on again.
The controller has stage auto-rotation programmed into it to equalize the 
run time between the stages. On a call for cooling, the first stage will be 
activated. If, after the time delay, the cooling load is not met, the second 
stage will start. When the cooling load is satisfied, the first stage will turn off 
and the second stage will continue to run.
Internal Economizer
Select between Inactive and Active. Internal economizer is recommended 
when the energy recovery unit provides 100% of the outdoor air. During 
economizer mode, the energy wheel is de-activated to enable “free-cooling”. 
Refer to page 4 to set the enthalpy at which economizer mode will be 
activated.
The controller also has external economizer capabilities. External economizer 
is recommended when the energy recovery unit is used in conjunction with 
an air-handling unit that has its own economizer section. When the energy 
recovery unit gets the economizer signal from the air handler, the supply 
blower, outdoor damper, and energy recovery wheel are de-energized. Refer 
to the wiring diagram on page 7 for wiring the external economizer contact 
into the controller.
Internal Economizer
Inactive
IG Furnace Settings
Min Time On: 2 MIN
IG Furnace Settings
(Visible with Indirect Fired Gas Furnace only)
Min Time On The minimum time the furnace stages on.