Installation of concentric venting, Concentric venting – horizontal, Vent connection diameter – Greenheck PVF/PVG Indirect Gas-Fired Heat Modules (474645) User Manual

Page 9: Vent length, Determine venting location, Attach mounting brackets

background image

Indirect Gas-Fired Heat Modules

9

®

NOTE

Vent piping is supplied by others and not supplied by
manufacturer.

Concentric venting allows the exhaust pipe and
combustion air pipe to pass through a single hole in the
roof or wall of the building. A concentric venting adapter
(CVA) is required for concentric venting.

The concentric venting adapter is designed for indoor
installations and should never be installed on the
exterior of the building.

The exhaust pipe must terminate with the vent terminal.
For horizontal venting, the combustion air pipe must
terminate with the combustion air guard. For vertical
venting, the combustion air pipe must terminate with
the inlet terminal. Depending on what was ordered, one
of these vent terminals will be provided in the optional
venting kit along with the concentric venting adapter
(CVA).

If venting vertically through the roof, refer to the vertical
concentric venting instructions. If venting horizontally
through the wall, refer to the horizontal concentric
venting instructions.

CVA-4

4-inch Concentric

Venting Adapter

CVA-6

6-inch Concentric

Venting Adapter

Top View

Exhaust Connection

Concentric Side

Combustion Air Connection

Concentric Side

Exhaust Connection

Non-Concentric Side

Combustion Air Connection

Non-Concentric Side

CVA

Concentric Venting – Horizontal

Refer to the diagram below for venting on horizontal
concentric systems. Maintain at least 12 inches from
the combustion air inlet guard to the exhaust vent
terminal (Dim. B). To prevent water from running into the
combustion air pipe and to allow for easy installation
of the combustion air inlet guard, the combustion air
pipe must terminate at least 2 inches from the exterior
surface of the outside wall (Dim. A).

Vent Connection Diameter

Vent terminals must be used (one vent terminal included
with each furnace). Construct the vent system as shown
in the drawings and refer to the table for the correct vent
connection diameters.

Vent Length

Refer to table for minimum and maximum vent lengths.
The total equivalent vent length must include elbows.
The equivalent length of a
4 inch elbow is 6 feet and
the equivalent length of a
6 inch elbow is 10 feet.

Determine Venting Location

Determine the location of the concentric venting adapter
(CVA) based on any clearances that must be maintained
(follow all codes applicable).

Attach Mounting Brackets

Attach field-supplied, corrosion-resistant, mounting
brackets to the CVA using corrosion-resistant sheet
metal screws.

Vent

Length

Minimum

(feet)

Maximum

(feet)

Horizontal

5

70

Non-Concentric Vent

Connection Diameter

Concentric Vent

Connection Diameter

Furnace Size

(MBH)

Exhaust

(inches)

Combustion Air

(inches)

Exhaust

(inches)

Combustion Air

(inches)

75-175

4

4

4

6

200-400

6

6

6

8

A = 2 inch minimum

B = 12 inch minimum

Pitch vent pipe
downward
from furnace
1/4 inch per foot

Mounting

Bracket

Mounting

Bracket

Exhaust

Vent

Terminal

EXHAUST

COMBUSTION AIR

Exterior

Wall

B

A

Combustion

Air Inlet Guard

Installation of Concentric Venting