1. Connect a manometer to either test port on the

burner manifold.

2. Send the unit to high fire.

3. Check the gas pressure at the manifold test port. The

recommended pressure is 3.5 in. wg for natural gas
or 10.0 in. wg for LP gas.

4. Adjust the high fire screw on the valve

that is connected to the port being tested.
Counterclockwise rotation will decrease the gas
pressure and clockwise rotation will increase the
pressure.

5. Send the furnace to low fire by disconnecting and

isolating the wire from the high fire terminal on the
valve.

6. Check the gas pressure at the manifold test port.

The recommended low fire manifold pressure is
7/8 in. wg for natural gas or 2.5 in. wg for LP.

7. Adjust the low fire screw on the valve being tested.

Counterclockwise rotation will decrease the gas
pressure and clockwise rotation will increase the gas
pressure.

With 8 Stage Combustion

IMPORTANT

8 staged turndown furnaces use a split burner
manifold and two 2-stage gas valves per furnace.
The high fire and low fire manifold pressure must be
checked and properly set on each manifold.

Two Stage

Valve

Two Stage

Valve

Split Burner

Manifold

Remote Temperature

Sensor

FX Controller

Ignition

Controller

8. Turn off furnace. Reconnect the wire to the high fire

terminal. Remove manometer and reinstall plug into
manifold test port.

9. Connect manometer to the other manifold test port

and repeat the high fire / low fire set up sequence on
the other gas valve.

10. Turn off furnace. Reconnect the wire to the high fire

terminal. Remove manometer and reinstall plug into
manifold test port.

11. Return to the normal operation.

1. Connect a manometer to the test port on the burner

manifold.

2. Send the unit to high fire.

3. Check the gas pressure at the manifold test port. The

recommended pressure is 3.5 in. wg for natural gas
or 10 in. wg for LP gas.

4. Adjust the high fire screw on the valve.

Counterclockwise rotation will decrease the gas
pressure and clockwise rotation will increase the
pressure.

5. Turn off furnace. Remove manometer and reinstall

plug into manifold test port.

6. Return the unit to normal operation.

Single Section

Burner Manifold

Single Stage

Valve

Remote Temperature

Sensor

A350

JOHNSON

CONTROLS

A350

Controller

Ignition

Controller

With Single Stage