Maintenance: sq / bsq, Belt/bearing maintenance bsq unit, Recommended relubrication frequency in months – Greenheck SQ and BSQ (477180) User Manual
Page 9

9
Centrifugal Inline Fans
®
Maintenance: SQ / BSQ
Installation and maintenance are to be performed only
by qualified personnel who are familiar with local codes
and regulations and who are experienced with this type
of equipment.
Motor maintenance is generally limited to cleaning
and lubrication (where applicable). Cleaning should be
limited to exterior surfaces only. Removing dust buildup
on motor housing ensures proper motor cooling.
Greasing of motors is only intended when fittings are
provided. Many fractional horsepower motors are
permanently lubricated and should not be lubricated
after installation. Motors supplied with grease fittings
should be greased in accordance with manufacturers’
recommendations. Where motor temperatures do not
exceed 104ºF (40ºC), the grease should be replaced
after 2,000 hours of running time as a general rule.
Wheels require very little attention when moving clean
air. Occasionally, oil and dust may accumulate causing
imbalance. When this occurs the wheel and housing
should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time
maintenance checks are performed prior to restarting
unit.
A proper maintenance program will help these units
deliver years of dependable service.
DANGER
Always disconnect, lock and tag power source before
servicing. Failure to disconnect power source can
result in fire, shock or serious injury.
DANGER
Pour écarter les risques d’incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l’installation ou l’entretien.
IMPORTANT
Uneven cleaning of the wheel will produce an out of
balance condition that will cause vibration in the fan.
WARNING
This unit should be made non-functional when
cleaning the wheel or housing (fuses removed,
disconnect locked off).
WARNING
L’appareil doit être rendu non opérationnel lors du
nettoyage de la turbine ou du caisson (fusibles retirés,
sectionneur verrouillé).
Grease Manufacturers
Manufacturer
Grease (NLGI #2)
U.S. Electric Motors
Grease No. 83343
Chevron U.S.A. Inc
Chevron SRI Grease #2
Mobil Oil Corporation
Mobilith
Mobil 532
Texaco, Inc.
Premium BRB #2
Texaco Multifak #2
Amoco Oil Co.
Rykon Premium #2
Exxon
Unirex N2
Shell
B Shell Alvania #2
Suggested Fan Bearing Greasing Intervals
Interval
(months)
Type of Service
1 to 3
Heavy duty in dirty, dusty locations; high ambient
temperatures; moisture laden atmosphere; vibration.
3 to 6
12 to 24 hours per day, heavy duty, or if moisture is
present
6 to 12
8 to 16 hours per day in clean, relatively dry
atmosphere
12 to 18
Infrequent operation or light duty in clean
atmosphere
Belt/Bearing Maintenance BSQ Unit
1. Belts tend to stretch after a period of time. They
should be checked periodically for wear and
tightness. When replacing belts, use the same type
as supplied with the unit.
2. Matched belts should always be used on units with
multi-groove pulleys.
3. For belt replacement, loosen the tensioning device
enough to allow removal of the belt by hand. Do not
force belts on or off. This may cause cords to break,
leading to premature belt failure.
4. Once installed, adjust belts as shown in “Pre-Start-
Up Checks.”
5. Shaft bearings can be classified in two groups:
relubricating and non-relubricating. All bearings on
standard model BSQ fans are factory lubricated
and require no further lubrication under normal
use (between -20ºF and 180ºF in a relatively clean
environment).
6. Units installed in hot, humid or dirty locations should
be equipped with special bearings. These bearings
will require frequent lubrication. Caution should be
employed to prevent overpacking or contamination.
7. Grease fittings should be wiped clean. The unit
should be in operation while lubricating. Extreme
care should be used around moving parts.
8. Grease should be pumped in very slowly until a
slight bead forms around the seal. A high grade
lithium base grease should be used.
Recommended Relubrication Frequency in
Months
NOTE: If unusual environment conditions exist (extreme
temperature, moisture or contaminants) more frequent
lubrication is required.
A good quality lithium base grease, conforming to NLGI
Grade 2 consistency, such as those listed here may be
used.