beautypg.com

Roperation: sq / bsq, Inspection: sq / bsq, Important – Greenheck SQ and BSQ (477180) User Manual

Page 8

background image

8

Centrifugal Inline Fans

®

IMPORTANT

The fan has been checked for mechanical noises at
the factory prior to shipment. If mechanical noise
should develop, suggested corrective actions are
offered in the Troubleshooting section.

IMPORTANT

Over-tightening will cause excessive bearing wear and
noise. Too little tension will cause slippage at start-up
and uneven wear.

IMPORTANT

Adjust (tighten) belt tension after the first 24-48 hours
of operation.

6. The adjustable motor pulley is factory set for the

RPM specified. Speed can be increased by closing
or decreased by opening the adjustable motor
sheave. Two groove variable pitch pulleys must be
adjusted an equal number of turns open or closed.
Any increase in speed represents a substantial
increase in the horsepower required by a unit. Motor
amperage should always be checked to avoid
serious damage to the motor when speed is varied.

Belt Span

Deflection = Belt Span

64

WRONG

WRONG

WRONG

CORRECT

G

C

lo

c

k

w

is

e

For BSQ Installation Instructions
Imperial
Used in the USA

For BSQ-M Installation Instructions
Metric
Used in China

Belt Span

Deflection = Belt Span

62.5

Figure 12

Figure 13

NOTE: Identical fasteners on opposing side must

also be loosened.

R

Operation: SQ / BSQ

1. Before starting up or operating fan, check all

fasteners for tightness. In particular, check the
setscrews in wheel hub (and pulleys, if applicable).

2. While in the OFF position or before connecting the

fan to power, turn the fan wheel by hand to be sure
it is not striking the venturi or any obstacle.

3. Start the fan and shut it off immediately to check

rotation of the wheel with directional arrow in the
motor compartment, see Figure 10.

4. When the fan is started, observe the operation and

check for any unusual noises.

5. With the system in full operation and all ductwork

attached, measure current input to the motor and
compare with the nameplate rating to determine if
the motor is operating under safe load conditions.

6. Keep inlets and approaches to fan clean and free

from obstruction.

Inspection: SQ / BSQ

Inspection of the fan should be conducted at the
first 30 minute and 24 hour intervals of satisfactory
operation.
30 Minute Interval
Inspect bolts, setscrews and motor mounting bolts.
Adjust and tighten as necessary.
24 Hour Interval
Check all internal components. On BSQ unit only,
inspect belt alignment and tension. Adjust and tighten
as necessary.